A few terms first
A fluorescent fixture has lamps (the tubes), lampholders (the sockets), and a ballast, which regulates current and provides the voltage to start the lamp. LEDs use a driver instead, which controls the current and regulates the power. A TLED (tubular LED) is an LED lamp with the same diameter, length, and base as a fluorescent tube, so it fits the existing sockets. A troffer is the rectangular fixture in a dropped-ceiling grid (DOE FEMP application guide).
The letters come from UL 1993, the safety standard for these lamps, which “differentiates among three different types of LED tube lamps: Types A, B and C” (UL).
Type A: plug and play on the old ballast
A Type A tube runs on the fixture’s existing ballast with no mechanical or electrical changes (DLC). The Department of Energy’s Federal Energy Management Program (FEMP) rates it fast to install and the lowest cost on parts and labor. The catch is the ballast (FEMP):
- It limits efficiency. FEMP calls Type A “the least efficient of the TLEDs.”
- Not every tube works on every ballast, and two identical fixtures can hold different ballasts.
- The ballast usually fails first. “Aging ballasts are likely to fail before the TLED fails,” and they can make some Type A tubes flicker. If your ballasts are more than five years old, FEMP doesn’t recommend a lamp-only Type A swap.
- Emergency fixtures need testing. Emergency lighting may not work with some Type A tubes.
At DOE’s own headquarters, about 35,000 troffers got Type A tubes. A ballast could run some tube wattages but not others, or work at one voltage but not another, and “the majority of ballasts were compatible with the TLEDs, but a few outliers were not.” Lighting energy fell by about half, from 29.4 W to 14.4 W per troffer, though the new tubes also put out less light (1,600 lumens per lamp, down from 2,550) in offices DOE says had been over-lit (DOE).
Type B: bypass the ballast, run on line voltage
A Type B tube has its driver built in. An electrician rewires the fixture to bypass the ballast and send line voltage straight to the sockets (DLC). With the ballast out of the circuit, it saves more energy than Type A (FEMP).
The trade-off is safety. FEMP says Type B carries “the highest safety risk” of the tube types, because line voltage (120 or 277 volts) now reaches the sockets, and “the shock could cause serious injury or death.” The installer must label the fixture: modified, shock hazard, no fluorescent lamps (FEMP). UL describes a second label naming the replacement lamp’s type, model, and maker, and how to get replacements (UL).
Wiring isn’t uniform, either. Researchers at Pacific Northwest National Laboratory (PNNL) found Type B tubes powered from one end or both, saw wiring change under the same model number, and warned that the wrong lamp at relamping can short at the socket (PNNL).
Type C: a separate driver
Type C replaces the ballast with a separate LED driver in the fixture, so the sockets carry only the driver’s low-voltage output (DLC). FEMP rates Type C safer than Type B, the most efficient of the tube types, and easier to add controls to. It still needs an electrician and a label, and it’s less efficient than a retrofit kit (FEMP).
Hybrid tubes (Type A/B)
A hybrid, or “dual mode,” tube runs on the existing ballast and can also run on line voltage once the fixture is rewired (DLC). You can install it on the ballast now and bypass the ballast when it dies, at which point the fixture needs the same rewiring and labels as Type B. UL says A/B tubes can be used to convert a fixture only if they were also evaluated as part of a certified retrofit kit and carry a dual Listing and Classification Mark (UL FAQ).
Retrofit kits and new fixtures
A retrofit kit keeps the fixture housing in the ceiling and replaces the lamps, ballast, and sockets with LED modules and new electronics (FEMP). Some kits are strips that leave the fixture’s optics in place; others replace the whole optical system with a panel that hides the old housing (DLC). FEMP rates kits more efficient than tubes, with better heat management, lower failure potential, and room for controls, at a higher cost for parts and labor.
The National Electrical Code requires retrofit kits to be listed, and a UL Certified kit installed per its instructions doesn’t void the fixture’s original listing. Expect a permit: jurisdictions typically require one, plus code-authority approval (UL FAQ).
A new fixture replaces everything. FEMP rates it the most expensive and slowest to install, with the most energy savings, the most room for controls, and the longest life. It may need work above the ceiling, and a one-for-one swap can over-light a room (FEMP). A photometric layout (a design that calculates the light levels a room will get) checks that first.
Some older ballasts contain PCBs, a hazardous substance that needs proper handling and disposal, which can add cost (FEMP).
Side by side
| Option | Ballast | Wiring and labels | Dimming and controls | A fit when |
|---|---|---|---|---|
| Type A tube | Stays; the tube runs on it | No rewiring | Only through an existing dimming ballast | Ballasts are under five years old and first cost matters most |
| Type B tube | Bypassed | Line voltage to the sockets; electrician; warning label | Depends on the tube | You accept line voltage at the sockets to drop the ballast cheaply |
| Type C tube | Replaced by a separate driver | Electrician; label; low voltage at the sockets | Easier than other tubes, through the driver | You want tubes and controls |
| Type A/B tube | Used until it fails, then bypassed | None at first; Type B rewiring and labels later | In Type A mode, depends on the ballast | You want to put off rewiring |
| Retrofit kit | Removed | Electrician; labels; housing stays | Room to add controls | You can’t or won’t open the ceiling |
| New fixture | Removed with the fixture | Electrician; may need work above the ceiling | The most room; controls can come built in | You’ll stay over five years and can work above the ceiling, or housings are damaged |
The last column draws on FEMP’s decision guide (FEMP).
Dimming and controls
With Type A, the lowest dim level you can reach depends on the existing ballast (DLC), and FEMP says adding dimming means changing the ballast. The DLC requires every lamp on its list to dim continuously or to have field-adjustable light output (a setting changed at the fixture), but notes that control claims come from manufacturers and aren’t verified. Retrofit kits offer more savings from controls than tubes (FEMP). Test whatever you pick with your dimmers: at DOE’s headquarters, “LED luminaires are not compatible with all dimmer switches” (DOE).
Rebates: check the DLC list, then check it again
The DesignLights Consortium (DLC) publishes Qualified Products Lists (QPLs) that, by its count, nearly 700 utility and energy-efficiency programs require for rebates (DLC). Its rules for tubes (DLC requirements):
- Type A, B, C, and dual-mode tubes and retrofit kits are listed in separate categories. Match the exact model and type.
- Tubes made for magnetic ballasts aren’t eligible, and neither are Type A tubes meant to replace T12 lamps. If your fixtures still run T12s on magnetic ballasts, a listed Type A tube isn’t an option.
- Type A tubes are tested on a reference ballast (for T8s, an instant-start ballast with a 0.88 ballast factor), so the listed figures reflect that ballast.
The list is changing: products not qualified to the DLC’s new requirements (SSL V6.0) will be delisted on December 15, 2026 (DLC). Check the QPL when you order, not just when you get the quote, and read your utility program’s rules before you buy.
How we can help
We convert fluorescent lighting to LED with tubes, retrofit kits, or new fixtures, and we recommend one after a free lighting audit of your building. Buildings over 75,000 sq ft may not qualify for a free audit. Our own licensed electricians do any rewiring, we do the utility rebate paperwork, and we recycle the old lamps and ballasts and give you the disposal certificates.
Read more about fluorescent to LED retrofits and lighting audits, estimate your savings with the savings calculator, or request a free lighting audit.
Sources
- LED Retrofit Kits, TLEDs, and Lighting Controls: An Application Guide (DOE/EE-1544, PNNL-SA-123952)U.S. Department of Energy, Federal Energy Management Program, March 2017
- U.S. Department of Energy Headquarters Lighting Retrofit (DOE/EE-1744, PNNL-SA-131359)U.S. Department of Energy, Federal Energy Management Program, February 2018
- The Lowdown on TLEDs (LightFair International presentation)Pacific Northwest National Laboratory, for the U.S. Department of Energy, April 26, 2016
- Safety Compliance of Luminaire Retrofits (white paper)UL Solutions, 2024
- FAQ: UL Certified LED Retrofit Luminaire Conversion KitsUL Solutions, Web page, read 2026-11-20
- Technical Requirements for LED Lighting: SSL V6.0 & LUNA V2.0DesignLights Consortium, Released November 3, 2025; updated April 15, 2026
- Transition to SSL V6.0 and LUNA V2.0 RequirementsDesignLights Consortium, Web page, read 2026-11-20
- DesignLights Consortium (DLC) Quick FactsDesignLights Consortium, Web page, read 2026-11-20